Simulation of water flow and tracer experiments for a clear water storage tank

Date

2010

Authors

Crowther, J.
Dandy, G.

Editors

Advisors

Journal Title

Journal ISSN

Volume Title

Type:

Conference paper

Citation

Proceedings of First European Congress of the IAHR, held in Edinburgh, UK 4-6 May 2010: pp.1-6

Statement of Responsibility

J. M. Crowther and G. C. Dandy

Conference Name

European Congress of the IAHR (1st : 2010 : Edinburgh, UK)

Abstract

This paper reports on tracer experiments and simulation results for Stromlo Water Treatment Plant in Canberra, Australia. Experimental data were collected from the tank using fluoride as a tracer. With the tank at a uniform initial fluoride concentration of 0.88 mg/L, the fluoride feeder was turned off for 5 hours and then turned back on. The fluoride concentration at the tank outlet was monitored throughout and the objective was to model it as accurately as possible. Flow through the tank has been simulated at the rated flow from the works of 3.7 m3/s using the PHOENICS computational fluid dynamics (CFD) program. The CFD simulation, with Chen and Kim turbulence model, agrees closely with the measured fluoride concentrations and requires no fitted parameters.